| technical handbooks | esp product range | questions & answers | furse news | introduction |

Electronic Systems Protection

furse
Furse ESP products are now available from the online catalogue click here
ESP 06E, ESP 15E, ESP 30E, ESP, 50E Twisted pair data communication, and signal line protectors with lower in-line resistance, higher current and higher bandwidth

Installation

Installation diagram

Connect in series with the data communication or signal line either near where it enters or leaves the building or close to the equipment being protected (eg within its control panel). Either way it must be very close to the systems earth star point. Install protectors either within an existing cabinet/cubicle or in a separate enclosure. If installing several protectors together these can be simultaneously mounted and earthed via a CME kit.

Suitable accessories

Simultaneously mount and earth up to 4 of these protectors on a CME 4, up to 8 on a CME 8, up to 16 on a CME 16 or up to 32 on a CME 32 - click here for details.


Enclosures suitable for up to two (WBX 2/G) or three (WBX 3/G) protectors, or a CME 4 and its associated protectors (WBX 4), CME 8 and protectors (WBX 8) or one or two CME 16 kits and protectors (WBX 16/2) can be found here.

Protectors installed on a combined mounting and earthing kit (CME 8) within a WBX 8 enclosure.

Electrical specification

 

ESP 06E
ESP 15E
ESP 30E
ESP 50E
Nominal voltage¹
6V
15V
30V
50V
Maximum working voltage²
7.79V
16.7V
36.7V
56.7V
Current rating (signal)
1.25A
1.25A
1.25A
1.25A
In-line resistance (per line ± 10%)
1.0ohm
1.0ohm
1.0ohm
1.0ohm
Bandwidth (-3dB 50ohm system)
1.5MHz
>10MHz
>10MHz
>10MHz

1 Nominal voltage (DC or AC peak) measured at <10µA (ESP 15E, ESP 30E, ESP 50E) and <200µA (ESP 06E).
2 Maximum working voltage (DC or AC peak) measured at <5mA leakage (ESP 15E, ESP 30E, ESP 50E), <10mA (ESP 06E).
Transient specification

 

ESP 06E
ESP 15E
ESP 30E
ESP 50E
Let through voltage (all conductors)1
5kV,10/700µs test to:
BS 6651:1999 Appendix C, Cat C-High
ITU (formerly CCITT) IX K17
10.8V
26.2V
44.3V
65.8V
Maximum surge current²
-per signal wire
-per pair
10kA
20kA
10kA
20kA
10kA
20kA
10kA
20kA
1 The maximum transient voltage let-through the protector throughout the test (+/-10%), line to line & line to earth. Response time <10ns.
2 Tested with 8/20µs waveshape to ITU (formely CCITT), BS 6651:1999 Appendix C.
Mechanical specification

 

ESP 06E
ESP 15E
ESP 30E
ESP 50D
ESP 50E
Temperature range
-25°C to +70°C
-25°C to +70°C
-25°C to +70°C
-25°C to +70°C
-25°C to +70°C
Connection type
Screw terminal
Screw terminal
Screw terminal
Screw terminal
Screw terminal
Connection size (stranded)
1.5mm²
1.5mm²
1.5mm²
1.5mm²
1.5mm²
Earth connection
M6 stud
M6 stud
M6 stud
M6 stud
M6 stud
Weight
-unit
-packaged (per 10)
0.08kg
0.85kg
0.08kg
0.85kg
0.08kg
0.85kg
0.08kg
0.85kg
0.08kg
0.85kg

Dimensions
Mechanical specification

PDF

ESP E Range Brochure

previous page
Furse ESP products are now available from the online catalogue click here

| technical handbooks | esp product range | questions & answers | furse news | introduction |


ISO 9001
More Information
UK UK Office
Tel: +44 (0)1245 600 560
Fax: +44 (0)1245 808 399
Email: info@keison.co.uk
USA USA Office
Tel:
+1 541 956 9929
Fax: +1 541 610 1646
Email: info@keison.com
Germany German Office
Tel:
+49 761 4787 184
Fax: +49 761 4787 100
Email: info@keison.de
ISO 140001
More Information


© Copyright 2008 Keison International Ltd - All Rights Reserved