Connect in series with the data communication or signal
line either near where it enters or leaves the building or close to
the equipment being protected (eg within its control panel). Either
way it must be very close to the systems earth star point. Install protectors
either within an existing cabinet/cubicle or in a separate enclosure.
If installing several protectors together these can be simultaneously
mounted and earthed via a CME kit.
Suitable accessories
Simultaneously mount and earth up to 4 of these protectors
on a CME 4, up to 8 on a CME 8, up to 16 on a CME 16 or up to 32 on
a CME 32 - click here for details.
Enclosures suitable for up to two (WBX 2/G) or three (WBX 3/G) protectors,
or a CME 4 and its associated protectors (WBX 4), CME 8 and protectors
(WBX 8) or one or two CME 16 kits and protectors (WBX 16/2) can be found
here.
Electrical specification
ESP 06E
ESP 15E
ESP 30E
ESP 50E
Nominal voltage¹
6V
15V
30V
50V
Maximum working voltage²
7.79V
16.7V
36.7V
56.7V
Current rating (signal)
1.25A
1.25A
1.25A
1.25A
In-line resistance (per line ±
10%)
1.0ohm
1.0ohm
1.0ohm
1.0ohm
Bandwidth (-3dB 50ohm system)
1.5MHz
>10MHz
>10MHz
>10MHz
1 Nominal voltage (DC or AC peak) measured at <10µA
(ESP 15E, ESP 30E, ESP 50E) and <200µA (ESP 06E).
2 Maximum working voltage (DC or AC peak) measured at <5mA leakage (ESP 15E, ESP 30E, ESP 50E), <10mA (ESP 06E).
Transient specification
ESP 06E
ESP 15E
ESP 30E
ESP 50E
Let through voltage (all conductors)1
5kV,10/700µs test to:
BS 6651:1999 Appendix C, Cat C-High
ITU (formerly CCITT) IX K17
10.8V
26.2V
44.3V
65.8V
Maximum surge current²
-per signal wire
-per pair
10kA
20kA
10kA
20kA
10kA
20kA
10kA
20kA
1 The maximum transient voltage let-through the protector
throughout the test (+/-10%), line to line & line to earth. Response time
<10ns.
2 Tested with 8/20µs waveshape to ITU (formely CCITT), BS 6651:1999
Appendix C.