| technical handbooks | esp product range | questions & answers | furse news | introduction |

Electronic Systems Protection

furse
ESP KT1, ESP KT2, ESP K10T1, ESP K10T2 & ESP KE10 Protectors for telephone and ISDN lines wth LSA-PLUS connections

Installation

Identify the lines requiring protection and plug-in the protector (ensuring the correct orientation) for a series connection. Plug ESP K10T1/2 directly into each connection strip requiring protection.

Installation of ESP K10T1/K10T2

ESP KT1/2 must be installed via the ESP KE10 earth bar. Clip an ESP KE10 on to the connection strip and plug an ESP KT1/2 in to each line on the strip that needs protecting.


installation of ESP KT1/KT

If the protectors' ratings are exceeded it will sacrifice itself and fail short circuit, taking the line out of commission - indicating it needs replacing and preventing subsequent transients from damaging equipment.

Electrical specification

 

ESP KT1
ESP KT2
ESP K10T1
ESP K10T2
Maximum working voltage
-line to earth
-Line to line
190V
190V
58V
5V
190V
190V
58V
5V
Current rating (signal)
300mA
300mA
300mA
300mA
In-line resistance (± 10%)
4.4ohms
4.4ohms
4.4ohms
4.4ohms
Bandwidth (-3db 50ohm system)
>50MHz
>50MHz
>50MHz
>50MHz
1 Maximum working voltage (DC or AC peak) measured at 95µA for ESP KT1 and ESP K10T1 and at 5µA for ESP KT2 and ESP K10T2.
2 Post transient recovery voltage >80V.
Transient specification

 

ESP KT1
ESP KT2
ESP K10T1
ESP K10T2
Let-through voltage¹
5kV 10/700µs test to:
BS6651:1999 Appendix C, Cat C-High
ITU (formerly CCITT) IX K17
-Line to line
-Line to earth
200V
200V
27V
80V
200V
200V
27V
80V
Maximum surge current²
-per signal wire
-per pair
5kA
10kA
5kA
10kA
5kA
10kA
5kA
10kA
1 The maximum transient voltage let-through the protector throughout the test (+/-10%), line to line & line to earth. Response time <10ns.
2 Tested with 8/20µs waveshape to ITU (formely CCITT), BS 6651:1999 Appendix C.
Mechanical specification

 

ESP KT1, ESP KT2
ESP K10T1, ESPK10T2
ESP KE10
Temperature range
-25°C to +70°C
-25°C to +70°C
-

Connection type
LSA-PLUS 'disconnection' connection strips (BT part number 237A)
Earth connection
Via ESP KE10 earth bar
Via integral clip
-
Weight
-unit
-packaged
0.01kg
0.12kg (per 10)
0.10kg
0.12kg
0.01kg
0.10kg (per 10)
Dimensions
Mechanical specification

PDF

ESP KT KT10T Brochure

previous page

| technical handbooks | esp product range | questions & answers | furse news | introduction |


ISO 9001
More Information
UK UK Office
Tel: +44 (0)1245 600 560
Fax: +44 (0)1245 808 399
Email: info@keison.co.uk
USA USA Office
Tel:
+1 541 956 9929
Fax: +1 541 610 1646
Email: info@keison.com
Germany German Office
Tel:
+49 761 4787 184
Fax: +49 761 4787 100
Email: info@keison.de
ISO 140001
More Information


© Copyright 2008 Keison International Ltd - All Rights Reserved