| Electrical Specification |
| |
ESP 06Q | ESP 15Q | ESP 30Q | ESP 50Q | ESP TNQ | ESP RTDQ |
| Nominal voltage (note 1) |
6V | 15V | 30V | 50V | * | 6V |
| Maximum working voltage (note 2) |
7.78V | 18.8V | 37.8V | 57.8V | 190V | 7.78V |
| Current rating (signal) | 750mA | 750mA | 750mA | 750mA | 300mA | 700mA |
| In-line resistance (per line +/-10%) |
1.0 ohm | 1.0 ohm | 1.0 ohm | 1.0 ohm | 4.3 ohm | 1.0 ohm |
| Bandwidth (-3dB 50ohm system) |
1MHz | 2.5MHz | 4MHz | 6MHz | >50MHz | 800kHz |
| 1 Nominal voltage (DC or AC peak) measured at <5µA
(ESP 15Q, ESP 30Q, ESP 50Q) and <200µA (ESP 06Q, ESP RTDQ). 2 Maximum working voltage (DC or AC peak) measured at <5mA leakage (ESP 15Q, ESP 30Q, ESP 50Q)), <10mA (ESP 06Q, ESP RTDQ) and <95µA (ESP TNQ). |
| Transient Specification |
| |
ESP 06Q | ESP 15Q | ESP 30Q | ESP 50Q | ESP TNQ | ESP RTDQ |
| Let-through voltage - all conductors (note 1) 5kV, 10/700µs test to: BS 6651:1999 Appendix C, Cat C-High ITU (formely CCITT) IX K17 |
10.8V | 26.2V | 44.3V | 65.8V | 200V | 10.5V |
| Maximum surge current (note 2) per signal wire per pair |
10kA 20kA |
10kA 20kA |
10kA 20kA |
10kA 20kA |
10kA 20kA |
10kA 20kA |
| 1 The maximum transient voltage let-through the
protector throughout the test (+/-10%) line to line and line to earth.
Response time <10ns. |
| Mechanical Specification |
| |
ESP 06Q | ESP 15Q | ESP 30Q | ESP 50Q | ESP TNQ | ESP RTDQ |
| Temperature range | -25°C to +70°C | -25°C to +70°C | -25°C to +70°C | -25°C to +70°C | -25°C to +70°C | -25°C to +70°C |
| Connection type | Plugable 12 way screw terminal | |||||
| Conductor size (stranded) | 2.5mm2 | 2.5mm2 | 2.5mm2 | 2.5mm2 | 2.5mm2 | 2.5mm2 |
| Earth connection | Via DIN rail or M5 threaded hole in base of unit | |||||
| Dimensions
|
||||||
| |
| |