Let-through voltage (all conductors)¹
5kV, 10/700µs test to:
BS 6651:1999 Appendix C, Cat C-High
ITU (formerly CCITT) IX K17
20V
20V
20V
Maximum surge current²
10kA
10kA
10kA
1 The maximum transient voltage let-through the protector
throughout the test (+/-10%). Response time <10ns. This let-through voltage
represents a deviation from the applied signal voltage , present at the
time of the test.
2 Tested with 8/20µs waveshape to ITU (formely CCITT), BS 6651:1999
Appendix C.