1 Maximum working voltage (DC or AC peak) measured at 1mA
leakage.
Transient Specification
ESP LN
ESP LN-4
ESP LN-8
ESP LN-8/16
ESP LN-16/16
Let-through voltage (note 1)
1.5kV, 10/700µs test to:
BS 6651:1999 Appendix C, Cat C-Low
ITU (formely CCITT) IX K17
12.5V
12.5V
12.5V
12.5V
12.5V
Maximum surge current (note 2)
350A
350A
350A
350A
350A
1 The maximum transient voltage let-through the protector
throughout the test (+/-10%) line to line and line to earth. Response
time <10ns.
2 Tested with 8/20µs waveshape to ITU (formely CCITT), BS 6651:1999
Appendix C.