Hawk 5000 Specifications |
| ANALOGUE MEASUREMENT CAPABILITY PER PHASE: |
Single or three phase power: kW, kVA, KVAr, KVArl, Power Factor, TRMS Amps, TRMS Volts, Frequency. |
| TRUE RMS MEASUREMENT |
Voltage and currents sampled at 10,000 samples per second. True and apparent power individually calculated. |
| INTEGRATION PERIOD |
User selectable: 2 seconds to 2 hours. |
| MONITORING METHOD: |
Current: via clamps with a.c. current output max. 1 amp output. Clamp ratio user defined. Voltage via mains input to Hawk5000. |
| STORAGE CAPACITY: |
Displayed on screen as survey parameters are defined. Maximum detail; 30 min. periods; seven weeks. |
| STATUS INDICATORS: |
Mains on this phase
Current/No current on this phase
CT reversed or wrong phase
Pulses detected
Phaser
Comms active
Logging active |
| SYSTEM ACCURACY: |
Better than 2% using CT1000 clamps |
| MINIMUM ACCURATELY MEASURABLE CURRENT: |
Typically 0.4 Amps using 1000:1 CT Clamps |
| PULSE INPUT ACCURACY: |
+/- 1 pulse. |
| DATA COMMUNICATIONS |
RS232, 9600 baud, error corrected. |
| POWER SUPPLY |
180 to 263v rms, 40 to 65 Hz |
| DIMENSIONS: |
285W x 223D x 65H |