| PNEUMATIC |
| *Output Signal |
See ordering information. Pressure range can be limited by resetting the locknuts provided |
| *Air Supply |
Oil free, dry air or other dry gases, filtered to better than 25 microns; at least 0.2bar (3psig) above output pressure to a maximum of 10bar (150psig, 1000kPa) |
| *Flow Capacity |
Up to 300nl/min (10scfm). High relief version available for applications requiring a rapid exhaust |
| *Air Consumption |
0.2 l/min (0.006scfm) at 1bar (15psig);
0.3 l/min (0.01scfm) at 1.7bar (25psig);
0.6 l/min (0.02scfm) at 4bar (60psig);
1.2 l/min (0.04scfm) at 8bar (120psig);
(typical values at maximum supply pressure) |
| *Response Time |
less than 0.2 seconds for 50% load change |
| *Regulation Accuracy |
% output change for 1bar/15psi supply pressure change at mid-range output; 0.1% (0.14bar/2-25psi), 0.05% (0.14-4bar/2-60psi), 0.02% (0.14-8bar/2-120psi) |
| *Sensitivity |
Better than 0.3mbar (0.005psi) |
| *Hysteresis and Repeatability |
Typically less than 0.05% setting at mid-range |
| *Temperature Effect |
Typically better than +/-1% change of full span between -20°C and +70°C |
| *Connections |
1/4" NPT female standard (plus two integral 1/4" NPT gauge ports); others on request |
| MODEL TYPES |
| *Handwheel |
Basic manostat unit with pressure adjusting handwheel; mounting in any attitude, integral mounting nut supplied |
| *Dial manostat |
Manual pressure loading unit combining a manostat regulator with 4" diameter gauge |
| *DIN manostat |
As above but with a DIN standard pressure gauge |
| *DMW |
Weatherproof version of dial manostat with 100mm diameter gauge; pneumatic connections taken to lower face of casing; surface or post mounting (yoke supplied suitable for a 50mm/2" diameter post); casing is polycarbonate, grey finish to IP55 |
| *Volume Boosting Air Relay (manual bias) |
Remote control of regulated pressures is possible with minimal air usage; positive or negative bias between pilot signal and regulated pressure can be set up of up to 2bar/30psig |
| PHYSICAL |
| *Operating Temperature |
-20°C to +70°C |
| *IP Rating |
IP65 |
| *Vibration |
The unit is unaffected by moderate vibration |
| *Material of Construction |
Zinc diecasting passivated and epoxy painted. Berylium copper capsule; Nitrile diaphragms |
| note: a small pressure (<2psig, 0.14bar) will show at the lower end of dial manostats gauge scale (due to regulator servo operation)
|
|
ORDERING INFORMATION |
| Handwheel
monostats |
Ourtput pressure |
|
Order code |
0.14 -1.7 bar, 2-25psig |
Standard |
53100200R |
High relief |
53120200R |
0.14 - 4 bar 2-60psig |
Standard |
53100300R |
High relief |
53120300R |
0.14 -8 bar, 2-120 psig
|
Standard |
53100400R |
High relief |
53120400R |
|
| Manual
bias relay |
Ourtput pressure |
|
Order code |
0.2-1 bar, 3-15psig |
Standard |
53220100R |
High relief |
53230100R |
0.14 - 8 bar, 2-120psig |
High relief |
53220400R |
Standard |
53230400R |
|
| Options to special order: Captured
bleed version of handwheel manostat suitable for natural gas applications
available. Factory fitting of a reduction gearbox to handwheel manostat
(change "00R" to "96R"). Yoke mounting for Weatherproof Manostat (change
"00R" to "10R"). Alternative pneumatic connections. Low pressure versions
of standard models. |
| Din
Dial / monostats |
Pressure range |
Scale |
Dial |
Din |
Weatherproof DMW |
0.2-1 bar, 3-15psig |
Dual |
53300100R |
53310100R |
53320100R |
0-2 bar, 0-30psig |
Dual |
53301200R |
53311200R |
T.B.A |
0-4 bar, 0-60psig |
Dual |
53301300R |
53311300R |
T.B.A |
0-8 bar, 0-120psig |
Dual |
53301400R |
53311400R |
53321400R |
0.2-1 bar |
0 - 100% |
53309000R |
53319000R |
53329000R |
3-15psig |
0 - 100% |
53309100R |
53319100R |
53229100R |
20-100kpa |
0 - 100% |
53309200R |
53319200R |
53329200R |
|
| Options to special order: Captured
bleed version of handwheel manostat suitable for natural gas applications
available. Factory fitting of a reduction gearbox to handwheel manostat
(change "00R" to "96R"). Yoke mounting for Weatherproof Manostat (change
"00R" to "10R").Special scale calibrations for Dial Manostats. Alternative
pneumatic connections. Low pressure versions of standard models.
Manually Operated
Brochure
Mechanically
Operated Brochure |