Watson Smith - Controlling Pressure Worldwide

MANOSTAT PRECISION PRESSURE
REGULATOR SERIES
R27 - REMOTE MANUAL AND AUTO/MANUAL
LOADING STATIONS

FEATURES

 Reliable, durable
 Visual display of set pressure
 Precise regulation
 Excellent setting sensitivity

GENERAL DESCRIPTION

Remote manual and auto/manual loading stations are designed for the remote control of pneumatic systems using a manostat regulator and different combinations of air switching valve and pressure gauge.



Manostat Remote Manual and Auto/Manual Loading Stations

Functional Symbol

Technical Data
PNEUMATIC
*Output Signal See ordering information. Minimum outlet pressure 0.1-0.14bar (1.5-2psig)
*Air Supply Oil free, dry air or other dry gases, filtered to better than 25 microns; at least 0.2bar (3psig) above output pressure to a maximum of 10bar (150psig, 1000kPa)
*Flow Capacity Up to 300nl/min (10scfm). High relief version available for applications requiring a rapid exhaust
*Air Consumption 0.2 l/min (0.006scfm) at 1bar (15psig);
0.3 l/min (0.01scfm) at 1.7bar (25psig);
0.6 l/min (0.02scfm) at 4bar (60psig);
1.2 l/min (0.04scfm) at 8bar (120psig);
(typical values at maximum supply pressure)
*Response Time less than 0.2 seconds for 50% load change
*Regulation Accuracy % output change for 1bar/15psi supply pressure change at mid-range output; 0.1% (0.14bar/2-25psi), 0.05% (0.14-4bar/2-60psi), 0.02% (0.14-8bar/2-120psi)
*Sensitivity Better than 0.3mbar (0.005psi)
*Hysteresis and Repeatability Typically less than 0.05% setting at mid-range
*Temperature Effect Typically better than +/-1% change of full span between -20°C and +70°C
*Connections 1/4" NPT female standard (plus two integral 1/4" NPT gauge ports); others on request
MODEL TYPES
(With panel mounting plate, 3mm thick, black painted finish with corner fixing straps)
*SP Manostat regulator plus 63mm diameter pressure gauge (phospher bronze Bourdon tube to BS1780); horizontal/vertical mounting
*SP2 As SP model but with a rotary 2 position, 3-way auto/manual valve; horizonta/vertical mounting; pressure gauge indicates manual set pressure only
*SP2G2 As SP2 model but with a second pressure gauge to measure auto signal pressure before switching; horizontal/vertical mounting
*SP2G2W Weatherproof SP2G2; surface/post mounting (yoke supplied suitable for a 50mm/2" diameter post)
PHYSICAL
*Operating Temperature -20°C to +70°C
*IP Rating IP65
*Vibration The unit is unaffected by moderate vibration
*Material of Construction Zinc diecasting passivated and epoxy painted. Berylium copper capsule; Nitrile diaphragms
note: a small pressure (< 2psig, 0.14bar) will show at the lower end of dial manostats gauge scale (due to regulator servo operation)

ORDERING INFORMATION

Ordering Information

PDF

Loading Stations Brochure



| Watson Smith |

ISO 9001
More Information
UK UK Office
Tel: +44 (0)1245 600 560
Fax: +44 (0)1245 808 399
Email: info@keison.co.uk
USA USA Office
Tel:
+1 541 956 9929
Fax: +1 541 610 1646
Email: info@keison.com
Germany German Office
Tel:
+49 761 4787 184
Fax: +49 761 4787 100
Email: info@keison.de
ISO 140001
More Information


© Copyright 2008 Keison International Ltd - All Rights Reserved