| Pneumatic
|
| *Output Signal |
See product selector |
| *Air Supply |
Oil free, dry air, filtered to 5
microns; at least 0.7bar above maximum required output pressure range
|
| *Flow Capacity |
Up to 300Nl/min (10scfm) |
| *Air Consumption |
< 4bar: 0.85 l/min (0.03scfm)
typical
> 4bar: 1.75 l/min (0.06scfm) typical |
| *Response Time (dependent on input
and output pressure) |
< 2bar/30psig: less than 0.5 seconds
for 10-90% step change
> 2bar/30psig: 2 seconds for 10-90% step change |
| *Total Error |
+/-0.5% of span (typical, independent
error includes the combined effect of non-linearity, hysteresis, deadzone
and repeatability) |
| *Temperature Effect |
Typically better than 0.1% span/°C
for span and zero over operating range |
| *Supply Sensistivity |
Better than 0.025% span output change
per % supply pressure change |
| *Connections |
1/4" NPT standard (others available
on request) |
| Physical
|
| *Operating Temperature |
-20°C to +70°C |
| *IP Rating |
IP65 in normal operation |
| *Electromagnetic Compatibility |
This is a passive electromagnetic
instrument and is unaffected by interfering high frequency signals |
| *Material of Construction |
Zinc diecasting passivated and epoxy
paint, nitrile diaphragms, stainless steel/nylon flapper nozzle and supply
valve |
| *Mass |
1500g |
| *Mounting Position |
Integral surface mounting bracket
provided for preferred vertical mounting. 50mm pipe mounting kit available
|
| Electrical
|
| *Electrical Signal |
See product selector |
| *Failure Mode |
Signal falls to bleed pressure when
electrical supply fails |
| *Connections |
30mm square connector DIN 43650 provided,
mountable in four directions (alternative connections available) |
|
Product Selector |
| Output
Pressure |
Input Signal
|
Options to specific order:
Alternative input signal ranges
Alternative pressure ranges
Conduit entry with flying leads
Junction box
Intrinsically safe certification
50mm pipe mounting bracket
1/8" NPT pneumatic connections
Captured bleed/exhaust
Reverse acting
Split range |
| 4-20mA |
1-10V |
| 0.2-1bar |
53402100R |
53442100R |
| 0.2-2bar |
5340049XR |
5344013XR |
| 0.2-4bar |
5340064XR |
t.b.a |
| 0.14-8bar (3 wire) |
53572400R |
53562400R |
| 3-15psig |
53400100R |
53440100R |
| 3-30psig |
5340017XR |
5344014XR |
| 3-60psig |
5340005XR |
5344003XR |
| 3-120psig (3 wire) |
53570400R |
53560400R |
| Standard models
are 2 wire; 3 wire units require 12-24V supply |
| Certification
|
| An intrinsically safe 100X model certified to
CENELEC EN50 020 (BS 5501 part 7) EEx ia llC T4 is available (Installation
with these models must comply with information given in BS 5345, parts
1 and 4)
All instruments are tested on the Watson Smith Automatic Testing System
and an individual test certificate is provided at no extra charge. Each
unit is tested for linearity, hysteresis, total error, settling error,
over pressure, air consumption, response time, calibration, insulation,